Volume 2, Issue 3, September 2017, Page: 51-61
Exergy Flow Destruction of an Ice Thermal Energy Storage Refrigeration Cycle
Badr Habeebullah, Mechanical Engineering, King Abdulaziz University, Jeddah, Saudi Arabia
Majed Alhazmy, Mechanical Engineering, King Abdulaziz University, Jeddah, Saudi Arabia
Nedim Turkmen, Mechanical Engineering, King Abdulaziz University, Jeddah, Saudi Arabia
Rahim Jassim, Technical Department, Saudi Electric Services Polytechnic (SESP), Baish, Jazan, Saudi Arabia
Received: Jul. 19, 2017;       Accepted: Aug. 1, 2017;       Published: Aug. 25, 2017
DOI: 10.11648/j.jeece.20170203.13      View  1922      Downloads  110
Abstract
A computational model based on exergy analysis of optimization of an ice-on coil thermal energy storage refrigeration cycle is developed in this paper. The method is based on exergy destruction analysis and optimization. As there are single and/or two phase refrigerant streams involved in the heat transfer and pressure drop in the compressor, condenser, expansion valve, evaporator, and between the ice tank and the environment, then there are irreversibilities or exergy destruction due to finite temperature difference and due to pressure losses. These two irreversibilities which represent the principles of components of the total irreversibilities are not independent and there is a trade-off between them. In this paper the effects of pressure drop ratio (PDR) in the evaporator and the condenser on the total number of exergy destruction units and the exergetic efficiency of a refrigeration cycle are determined. The pressure drop irreversibility to the total irreversibility for ΔPcond =25 → 100 kPa and PDR =1 are determined to be 7.45% → 27.08%.
Keywords
Refrigeration Cycle, Exergy Analysis, Exergy Destruction, Optimization, Ice Storage
To cite this article
Badr Habeebullah, Majed Alhazmy, Nedim Turkmen, Rahim Jassim, Exergy Flow Destruction of an Ice Thermal Energy Storage Refrigeration Cycle, Journal of Energy, Environmental & Chemical Engineering. Vol. 2, No. 3, 2017, pp. 51-61. doi: 10.11648/j.jeece.20170203.13
Copyright
Copyright © 2017 Authors retain the copyright of this article.
This article is an open access article distributed under the Creative Commons Attribution License (http://creativecommons.org/licenses/by/4.0/) which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Reference
[1]
R. Yumrutas, M. Kunduz, and M. Kanoglu, Exergy analysis of vapor compression refrigeration systems, Exergy, an international Journal, No. 2, pp 266-272, 2002.
[2]
A. Bejan, Theory of heat transfer-irreversible refrigeration plants, J. Heat Mass Transfer 32 (9), pp 1631-1639, 1989.
[3]
W. Leidenfrost, K. H. Lee, and K. H. Korenic, Conservation of energy estimated by second law analysis of power-consuming process, Energy (5), pp 47-61, 1980.
[4]
J. Chen, X. Chen, and C. Wu, Optimization of the rate of exergy output of multistage endoreversible combined refrigeration system, Exergy, An International Journal, 1, (2) pp100-106, 2001.
[5]
Q. Chen, and R. C. Prasad, Simulation of a vapour-compression refrigeration cycles using HFC134a and CFC12, Int. Comm. Heat Mass Transfer, Vol 26, No 4 pp 513-521, 1999.
[6]
E. Bilgen and H. Takahashi, Exergy analysis and experimental study of heat pump systems, Exergy, An International Journal, 2, (4) pp259-265, 2002.
[7]
B. A. Habeebullah, Economic feasibility of thermal energy storage systems, Energy and Buildings 39 (2007) 355–363.
[8]
D. MacPhee, I. Dincer, Performance assessment of some ice TES systems, International Journal of Thermal Sciences 48 (2009) 2288–2299.
[9]
I. Dincer, M. A. Rosen, Energetic, environmental and economic aspects of thermal energy storage systems for cooling capacity, Applied Thermal Engineering 21 (2001) 1105–1117
[10]
Jekel TB, Mitchell JW, Klein SA. Modeling of ice storage tanks. ASHRAE Transactions 1993; 99: 1016-1024
[11]
K. A. Klein, and F. L. Alvarado, EES, Engineering equation solver (2007), Version 7.933, F-Chart Software, WI. USA.
[12]
A. C. Cleland, D. J. Cleland, and S. D. White, Cost-Effective Refrigeration, A five day Teaching Workshop. Institute of Technology and Engineering, Massey University, New Zealand, 2000.
[13]
T. J. Kotas, The exergy method of thermal plant analysis”. Reprinted, Krieger, Malabar, Florida, USA, 1995.
[14]
A. Bejan, Advanced engineering thermodynamics” John Willey, New York, USA, 1997.
[15]
A. L. London, and R. K. Shah, Cost of irreversibilities in heat exchangers design, Heat Transfer Engineering, Vol. 4, No. 2, pp 59-73, 1983.
[16]
C. F. Tapia, and M. J. Moran, Computer-Aided Design and optimization of heat exchangers”, Computer-Aided Engineering of Energy Systems, Vol. 1-Optimization ASME, pp 93-103, 1986.
Browse journals by subject